Description
140AMM09000
| range of product | Modicon Quantum automation platform | |
|---|---|---|
| product or component type | Input/output analog module | |
| type of filter | Single pole low pass – 3 dB at 21 Hz +/- 20 % input circuit |
| I/O modularity | 6 channels | |
|---|---|---|
| addressing requirement | 2 output words 5 input words |
|
| analogue input number | 4 | |
| analogue input type | Bipolar current +/- 20 mA 15 bits DC Bipolar voltage +/- 10 V 16 bits DC Bipolar voltage +/- 5 V 15 bits DC Unipolar current 0…20 mA 15 bits DC Unipolar offset current 4…20 mA 14 bits DC Unipolar offset voltage 1…5 V 14 bits DC Unipolar voltage 0…10 V 16 bits DC Unipolar voltage 0…5 V 15 bits DC |
|
| absolute maximum input | +/- 25 mA current +/- 50 V voltage |
|
| input impedance | > 10 MOhm voltage > 250 Ohm current |
|
| offset | +/- 0.0014 % of full scale maximum/°C 0…60 °C input circuit | |
| gain shift | +/- 0.002 of full scale maximum 0…60 °C input circuit | |
| common mode rejection | > 80 dB 50/60 Hz input circuit | |
| analogue output number | 2 | |
| analogue output range | 4…20 mA | |
| analogue output resolution | 12 bits | |
| loop voltage | 0…60 V DC with external resistance output circuit 7…30 V DC output circuit |
|
| voltage drop | 30 V DC 20 mA | |
| setting time | 900 µs to +/- 0.1 % of the final value output circuit | |
| external power requirement | 7…30 V output circuit | |
| absolute accuracy error | +/- 0.03 % at 25 °C input circuit +/- 0.05 % of full scale maximum at 25 °C input circuit +/- 0.20 % of full scale at 25 °C output circuit +/- 0.004 % of full scale at 0…60 °C output circuit +/- 0.007 %/°C of full scale maximum at 0…60 °C output circuit |
|
| linearity | 2.4 % over and under range voltage 2.4 % over range, and – 9.6 % under range current Monotonic +/- 1 LSB input Monotonic +/- 1 LSB output |
|
| update time | 15 ms output circuit 320 ms input circuit |
|
| fault type | Open circuit input/output circuit Overtacking scale (unipolar) input circuit Status byte output circuit |
|
| isolation between channels | 500 V AC for 1 minute 750 V DC for 1 minute |
|
| isolation between channels and bus | 500 V AC for 1 minute 750 V DC for 1 minute |
|
| isolation between input channel and output channel | 500 V for 1 minute 750 V for 1 minute |
|
| marking | CE | |
| local signalling | 1 LED green bus communication is present (Active) 1 LED red external fault 6 LEDs green channel is turned on 6 LEDs red channel fault |
|
| bus current requirement | 350 mA | |
| module format | Standard | |
| product weight | 0.3 kg |
| product certifications | C-Tick.1 FM Class 1 Division 2 |
|
|---|---|---|
| standards | CSA C22.2 No 142 UL 508 |
|
| resistance to electromagnetic fields | 10 V/m 80…2000 MHz conforming to IEC 801-3 | |
| ambient air temperature for operation | 0…60 °C | |
| ambient air temperature for storage | -40…85 °C | |
| relative humidity | 95 % without condensation | |
| operating altitude | <= 5000 m |